Arc Flash Analytic for Windows
Key Details of Arc Flash Analytic
- Calculate incident energy and arc flash and shock protection boundaries in electrical equipment.
- Last updated on 1/24/2019
- There have been 7 updates
- Virus scan status:
Clean (it's extremely likely that this software program is clean)
Developer's Description
The IEEE 1584 empirically derived model was chosen for arc flash analysis due to the model's capability to accurately account for a wide variety of setup parameters including:Voltages in the range of 208 V to 15 000 V, three-phase (line-to-line).Frequencies of 50 Hz or 60 Hz.Bolted fault current (rms symmetrical):208 V - 600 V : 500 A to 106 000 A;601 V - 15 000 V : 200 A to 65 000 A;Gaps between conductors:208 V - 600 V : 6.35 mm (0.25 in) to 76.2 mm (3 in.);601 V - 15 000 V : 19.05 mm (0.75 in) to 254 mm (10 in.);Working distances of 305 mm (12 in) or larger;Fault clearing time: no limit.Enclosure dimension limits:Maximum Height or Width: 1244.6 mm (49 in.);Maximum Opening Area: 1.549 m2 (2401 in2);Minimum Width: The width of the enclosure should be larger than four times the gap between conductors (electrodes).Electrode Configurations:VCB: Vertical conductors/electrodes inside a metal box/enclosure;VCBB: vertical conductors/electrodes terminated in an insulating barrier inside a metal box/enclosure;HCB: horizontal conductors/electrodes inside a metal box/enclosure;VOA: vertical conductors/electrodes in open air;HOA: horizontal conductors/electrodes in open air.